VdS Schadenverhuetung Zertifikate

Certificate

G417003

Not system-bound


Telefon

Minimax GmbH


Industriestraße 10 - 12
DE 23840 Bad Oldesloe
Telefon 04531/8030
fax 04531/803-248

vds
DIN CEN/TS 14972 (DIN SPEC 91216):2011-09
VdS 2344:2014-07 - Procedure guidelines

Com­po­nents for water ex­tin­gui­shing systems
'MXD-V13-K2,0-XP'
High pressure water mist nozzle

Related Systems
Updated at: 03.05.2024
The water mist nozzle 'MXD-V13-K2,0-XP' may only be used to protect areas of application according to VdS 3188 Annex K.2.3:

- paint booths

Parameter water mist nozzle (painting line):
- maximum permissible ceiling height: 6,0 m

Limitations and restrictions:
- flammable liquids with a flash point greater or equal + 21°C
- less dangerous liquids with regard to their flammability or their fire behavior
- The area above the nozzle level must be free of fire loads such as cable ducts (exception: interior protective coverings such as films).

The annex 3 of the approval and the system-specific manual for planning and installation of the manufacturer must be observed.
    . up
    Top