Certificate

S4060013


"EconAqua"
Low pressure water mist system

Telefon

Minimax Technologies GmbH


Industriestraße 10/12
DE 23840 Bad Oldesloe
Telefon +49 4531 803-0
Email webmaster@minimax.de

vds
EN 14972-5:2024 - Water mist systems, Part 5: Test protocol for car garages for automatic nozzle systems
EN 14972-6:2023 - Water mist systems, Part 6: Test protocol for false floors and false ceilings for automatic nozzle systems
VdS 2562:2013-03 - Procedure for the approval of new extinguishing technologies

Com­po­nents for water ex­tin­gui­shing systems
Related Products

The fine spray fire extinguishing system type 'EconAqua' may be used only for the protection of the risks/areas specified below according to VdS CEA 4001.

Maximum allowable ceiling height depending on fine spray and the field of application

  • Office- / Hotel areas: 2,8 m to 5 m ceiling height
  • False ceilings and false floors: 0,3 m to 0,8 m
  • Parking garages: 2,7 m ceiling height

    OH1 hazards without size restrictions:
  • Office areas: Offices, banks, conference rooms, schools, universities, churches, prison- and reformatory institutions, restaurants as well as similar OH1 hazards.
    (kitchen areas only if it is verified by additional spray tests that the water cannot hit the oil and sufficient protection is granted), stations and counter areas (sales areas, shopping malls, storages etc. are not included.
  • Hotel areas: Hotels, hospitals, foster homes, old people¿s homes, residential homes for the elderly and residential apartments
  • False ceilings and false floors with a height of 300 mm to 800 mm
    (Raw ceilings/raised floors including mounting not flammable, cables with a layout density < 40% of the base area and a fire load > 12,6 MJ/m²)

    Size limitation = 50 m² as protection of buildings, fire-resistant separated (protection of content and facility is not included):
    Store rooms (no storage of flammable liquids, gases etc., synthetics to a limited extent) computer rooms, technics rooms, libraries, file rooms, archives and similar.

    OH2-parking garages
    Protection of non-automatic, all side enclosed parking garages and basement garages (OH2).

    Annex 3 of the VdS-Approval and the installation manual of the manufacturer have to be observed.