Certificate
G416021
Not system-bound
Tyco Fire Protection Products
1467 Elmwood Ave
US 02910 Cranston, RI
VdS 2344:2014-07 - Procedure guidelines
VdS 3100-46:2022-08 - Sprinkler nozzles for the use in water mist systems, Requirements and test methods
Components for water extinguishing systems
AM30
Low pressure water mist sprinkler
The sprinkler AM30 may only be used to protect suspended ceilings and floors.
Sprinkler parameters:
- max. permissible ceiling height: 0.3 - 0.8 m
Further restrictions: - The raw ceiling including the suspension as well as the floor must consist of non-combustible building materials.
- Raised floors must be made of fire-retardant material.
- No fire load may be placed above the sprinklers.
- Cable routes in the area of raised floors or false ceilings may only be occupied by < 40 % of the area of the routes.
- Media lines for the transport of flammable substances are not permitted.
- The protection of false ceiling areas used as ventilation systems is not permitted.
Annex 3 of the approval and the manufacturer's installation manual must be observed.