Certificate
G416021
Not system-bound
Tyco Fire Protection Products
1467 Elmwood Ave
US 02910 Cranston, RI
401-781-8220
401-781-7317
VdS 2344:2014-07 - Procedure guidelines
VdS 3100-46:2022-08 - Requirements and test methods
Components for water extinguishing systems
AM30
Low pressure water mist sprinkler
Updated at: 04.05.2024
The sprinkler AM30 may only be used to protect suspended ceilings and floors.
Sprinkler parameters:
- max. permissible ceiling height: 0.3 - 0.8 m
Further restrictions:
- The raw ceiling including the suspension as well as the floor must consist of non-combustible building materials.
- Raised floors must be made of fire-retardant material.
- No fire load may be placed above the sprinklers.
- Cable routes in the area of raised floors or false ceilings may only be occupied by < 40 % of the area of the routes.
- Media lines for the transport of flammable substances are not permitted.
- The protection of false ceiling areas used as ventilation systems is not permitted.
Annex 3 of the approval and the manufacturer's installation manual must be observed.