Tyco Fire Protection Products


1467 Elmwood Ave
US 02910 Cranston, RI
Telefon 401-781-8220
fax 401-781-7317

vds
VdS 2344:2014-07 - Procedure guidelines
VdS 3100-46:2022-08 - Requirements and test methods

Com­po­nents for water ex­tin­gui­shing systems
AM30
Low pressure water mist sprinkler

Updated at: 04.05.2024
The sprinkler AM30 may only be used to protect suspended ceilings and floors.

Sprinkler parameters:
- max. permissible ceiling height: 0.3 - 0.8 m

Further restrictions:
- The raw ceiling including the suspension as well as the floor must consist of non-combustible building materials.
- Raised floors must be made of fire-retardant material.
- No fire load may be placed above the sprinklers.
- Cable routes in the area of raised floors or false ceilings may only be occupied by < 40 % of the area of the routes.
- Media lines for the transport of flammable substances are not permitted.
- The protection of false ceiling areas used as ventilation systems is not permitted.

Annex 3 of the approval and the manufacturer's installation manual must be observed.