VdS Schadenverhuetung Zertifikate

Certificate

G416021

Not system-bound


Telefon

Tyco Fire Protection Products


1467 Elmwood Ave
US 02910 Cranston, RI
Telefon 401-781-8220
fax 401-781-7317

vds
VdS 2344:2014-07 - Procedure guidelines
VdS 3100-46:2022-08 - Sprinkler nozzles for the use in water mist systems, Requirements and test methods

Com­po­nents for water ex­tin­gui­shing systems
AM30
Low pressure water mist sprinkler

The sprinkler AM30 may only be used to protect suspended ceilings and floors.

Sprinkler parameters:

  • max. permissible ceiling height: 0.3 - 0.8 m

    Further restrictions:
  • The raw ceiling including the suspension as well as the floor must consist of non-combustible building materials.
  • Raised floors must be made of fire-retardant material.
  • No fire load may be placed above the sprinklers.
  • Cable routes in the area of raised floors or false ceilings may only be occupied by < 40 % of the area of the routes.
  • Media lines for the transport of flammable substances are not permitted.
  • The protection of false ceiling areas used as ventilation systems is not permitted.

    Annex 3 of the approval and the manufacturer's installation manual must be observed.