VdS Schadenverhuetung Zertifikate

Certificate

S419003


'MSPU/EPU/LPU'
High pressure water mist system

Telefon

Marioff Corporation Oy


Plaza Business Park Halo; Äyritie 24
FI 01511 Vantaa
Telefon +358505628831

vds
VdS 2562:2013-03 - Procedure for the approval of new extinguishing technologies

Com­po­nents for water ex­tin­gui­shing systems
Related Products

The high-pressure water mist system may only be used to protect the following risks/areas according to VdS 3188 annex K.1.1, K.1.2, K.1.4:

Protection of office areas (K.1.1) and occupied areas (K1.2) with high pressure water mist sprinklers 'C10-xxC/0', 'C20-xxC/0' and 'C30-xx*C/0' (depending on nominal release temperature).

Parameter High pressure water mist sprinkler 'C10-xxC/0':
-maximum permissible ceiling height: 2.5 m

Parameter High pressure water mist sprinkler 'C20-xxC/0':
-maximum permissible ceiling height: 3.5 m

Parameter High pressure water mist sprinkler 'C30-xxC/0':
-maximum permissible ceiling height: 4.0 m

Protection of false ceilings and false floors (K.1.4) with high pressure water mist sprinkler 'C12-xx
C/0' (*dependent on nominal release temperature).

Parameter High pressure water mist sprinkler 'C12-xxC/0':
-maximum permissible ceiling height: 0.3 - 0.8 m

The special requirements for the arrangement of the water mist nozzles and the minimum operating time must be observed.