"FTS-CU"
High pressure water mist system
FOGTEC Brandschutz GmbH
Schanzenstraße 19 A
DE 51063 Köln
VdS 2344:2014-07 - Procedure guidelines
VdS 2562:2013-03 - Procedure for the approval of new extinguishing technologies
Components for water extinguishing systems
Related Products
Updated at: 08.05.2026
The high pressure water mist system may only be used to protect the following risks/areas according to VdS 3188 annex K.2.2:
Protection of machinery spaces with a maximum volume of the protected area of
4.4 m³ with high pressure water mist nozzle 'DK4-12-O'.
Parameters:
-maximum permissible volume of the protected area: 4.4 m³.
-maximum permissible nozzle distance: 2.0 m
-maximum permissible wall distance: 0.75 m
The planning and installation instructions of the manufacturer (see enclosure 2) have to be observed.