VdS Schadenverhuetung Zertifikate

Certificate

S412002


"ProCon XP"
High pressure water mist system

Telefon

Minimax GmbH


Industriestraße 10 - 12
DE 23840 Bad Oldesloe
Telefon 04531/8030
fax 04531/803-248

vds
VdS 2344:2014-07 - Procedure guidelines
VdS 2562:2013-03 - Procedure for the approval of new extinguishing technologies

Com­po­nents for water ex­tin­gui­shing systems
Related Products
Updated at: 02.05.2024
The high pressure water mist system may only be used to protect the following risks/areas according to VdS 3188 annex K.2.2:

Protection of machine rooms with a maximum volume of the protection area of 260 m³ with high pressure water mist nozzle 'MXD-V12-K0,63-XP'.

Parameters:
-maximum permissible volume of the protection zone: 260 m³.
-maximum permissible ceiling height: 5.0 m

The special requirements for the arrangement of the water mist nozzles and the minimum operating time must be observed.

The installation, operating and maintenance instructions (see annex 2) must be observed.