Certificate
S412002
"ProCon XP"
High pressure water mist system
Minimax GmbH
Industriestraße 10 - 12
DE 23840 Bad Oldesloe
04531/8030
04531/803-248
VdS 2344:2014-07 - Procedure guidelines
VdS 2562:2013-03 - Procedure for the approval of new extinguishing technologies
Components for water extinguishing systems
Related Products
- G211052 - Minimax GmbH - FMZ 5000 mod S
- G219048 - Minimax GmbH - FMZ6000 BMZ/EST
- G417006 - Minimax GmbH - 'MXD-V12-K0,63-XP'
- G205019 - Minimax GmbH - FMZ 5000 EST
- G204124 - Minimax GmbH - FMZ 5000 BMZ/EST
- G220012 - Minimax GmbH - FMZ6000 EST
Updated at: 02.05.2024
The high pressure water mist system may only be used to protect the following risks/areas according to VdS 3188 annex K.2.2:
Protection of machine rooms with a maximum volume of the protection area of 260 m³ with high pressure water mist nozzle 'MXD-V12-K0,63-XP'.
Parameters:
-maximum permissible volume of the protection zone: 260 m³.
-maximum permissible ceiling height: 5.0 m
The special requirements for the arrangement of the water mist nozzles and the minimum operating time must be observed.
The installation, operating and maintenance instructions (see annex 2) must be observed.