S4040003


"GPU"
High pressure water mist system

Telefon

Marioff Corporation Oy


Plaza Business Park Halo; Äyritie 24
FI 01511 Vantaa
Telefon +358505628831

vds
VdS 2344:2014-07 - Procedure guidelines
VdS 2562:2013-03 - Procedure for the approval of new extinguishing technologies

Com­po­nents for water ex­tin­gui­shing systems
Related Products
Updated at: 04.05.2024
The high pressure water mist system may only be used to protect the following risks/areas according to VdS 3188 Annex K.2.2:

Protection of machine rooms with a maximum volume of the protective area of
500 m³ with high pressure water mist nozzle '4S 1MC 8MC 1000'.

Parameters:
-maximum permissible volume of the protection zone: 500 m³.
-maximum permissible ceiling height: 5.6 m

The special requirements for the arrangement of the water mist nozzles and the minimum operating time must be observed.

The installation, operating and maintenance instructions (see annex 2) must be observed.