Certificate
S4060001
"FTS-PU" und / and "FTS-PU NG"
High pressure water mist system
FOGTEC Brandschutz GmbH
Schanzenstraße 19 A
DE 51063 Köln
VdS 2562:2013-03 - Procedure for the approval of new extinguishing technologies
Components for water extinguishing systems
Related Products
The high pressure water mist system may only be used to protect the following risks/areas according to VdS 3188 annex K.2.4
Parameter High pressure water mist nozzle:
- maximum permissible ceiling height: 5.5 m
Scope of recognition:
Protection of warehouses and production facilities with flammable liquids.
Restrictions and limitations:
-Storage of liquids with a flash point equal to or greater than -4°C (reference heptane) or liquids less hazardous in terms of flammability and combustibility (for exceptions see P&E manual)
-Storage of metal containers with a maximum size of 200 litres
-Storage exclusively in non-flammable shelves with water-permeable intermediate floors on pallets
Annex 3 and the system-specific manual for planning and installation of the manufacturer must be observed.
Updated at: 20.09.2026