VdS Schadenverhuetung Zertifikate

Certificate

G417061

Not system-bound


Telefon

Fagus-GreCon Greten GmbH & Co. KG


Hannoversche Straße 58
DE 31061 Alfeld
Telefon 0049 (0)5181 79-0
fax 0049 (0) 5181 79-229

vds
DIN CEN/TS 14972 (DIN SPEC 91216):2011-09
VdS 2344:2014-07 - Procedure guidelines

Com­po­nents for water ex­tin­gui­shing systems
"DBNM22"
Low pressure water mist nozzle

Related Systems
Updated at: 03.05.2024
The nozzle BNM22 may be used only to protect the following areas of a continuous press of the wood-based panel industry:
- drip tray

provided that in these areas:
- wood shavings, wood fibers or less dangerous substances with regard to their flammability and their fire behavior do occur, and
- flammable liquids with a flash point> = + 55 ° C are used.
It has to be installed as many nozzles as necessary to ensure that the entire shelter (including cavities) is charged with water.

Uncontrolled spread of fire (for example by spray fire) should be avoided by:
- immediate interruption of the supply of means of production, lubricating oils, thermal oils, etc.
- shutdown of the suction devices, ventilators, fans and heaters.

Storage in the areas listed above or immediately adjacent areas without structural separation is not permitted.

The installation, operating and maintenance instructions (see enclosure 2) must be observed.
    . up