VdS Schadenverhuetung Zertifikate

Certificate

S420001


"FTS-PU" und/and "FTS-PU NG"
High pressure water mist system

Telefon

FOGTEC Brandschutz GmbH


Schanzenstraße 19 A
DE 51063 Köln
Telefon 0221/96223-31
fax 0221/96223-30

vds
VdS 2344:2014-07 - Procedure guidelines
VdS 2562:2013-03 - Procedure for the approval of new extinguishing technologies

Com­po­nents for water ex­tin­gui­shing systems
Related Products
Updated at: 07.05.2024
The high pressure water mist system may only be used to protect the following risks/areas according to VdS 3188 annex K.2.2:

Protection of machinery spaces with a maximum volume of the protected area of
1070 m³ with high pressure water mist nozzle 'DK9N-26/23/26-O'.

Parameters:
- Maximum permissible volume of the protected area: 1070 m³.
- maximum permissible ceiling height: 10.0 m

The planning and installation instructions of the manufacturer (see annex 2) have to be observed.