Certificate
G4090007
Not system-bound
Tyco Building Services Products B.V. (trading as "Tyco Fire & Building Products" and "Johnson Controls")
Kopersteden 1
NL 7547 TJ Enschede
+31-53-4284444
0031/53/4283377
EN 12259-1:1999 + A1:2001 + A2:2004 + A3:2006 - Sprinklers
VdS 2100-25:2008-01 - Requirements and test methods
VdS 2344:2014-07 - Procedure guidelines
Components for water extinguishing systems
"RF II-CCP"
Concealed glass bulb sprinkler, K80
Updated at: 03.05.2024
DN 15 68, 93 °C
Due to the design the Sprinkler type 'RF II-CCP' shall not be installed in false ceilings in which the false ceiling space is protected by a water extinguishing system.
Due to the design the Sprinkler type 'RF II-CCP' shall not be installed in false ceilings in which during a fire the pressure above the false ceiling may be assumed to be higher than the pressure below the false ceiling.
Due to the design the Sprinkler type 'RF II-CCP' shall not be installed in solid ceilings.
The criterion for the dropping of the cover relevant for this approval is heat.