VdS Schadenverhuetung Zertifikate

Certificate

G417007

Not system-bound


Telefon

Minimax GmbH


Industriestraße 10 - 12
DE 23840 Bad Oldesloe
Telefon 04531/8030
fax 04531/803-248

vds
DIN CEN/TS 14972 (DIN SPEC 91216):2011-09
VdS 2344:2014-07 - Procedure guidelines

Com­po­nents for water ex­tin­gui­shing systems
'MX3-WM07'
High pressure water mist sprinkler

Related Systems
Updated at: 03.05.2024
The water mist sprinkler 'MX3-WM07' may only be used to protect the following areas of application according to VdS 3188 Annex K.2.3:

- Adjacent areas of painting booths such was dryers, preparation, evaporation or displacement areas in which no painting operations take place.

Parameter water mist sprinkler:
- maximum permissible ceiling height: 6 m

Storage of flammable liquids or other flammable materials in the protected areas is not permitted.

For the protection of rail and dockhouses as well as paint supply channels special requirements apply to the installation of the water mist sprinklers according to the system-specific manual for planning and installation.

The protection of paint booths is not permitted.

The annex 3 of the approval and the system-specific manual for planning and installation of the manufacturer must be observed.
    . up
    Top