VdS Schadenverhuetung Zertifikate

Certificate

G417002

Not system-bound


Telefon

Minimax Technologies GmbH


Industriestraße 10/12
DE 23840 Bad Oldesloe
Telefon +49 4531 803-0
Email webmaster@minimax.de

vds
DIN CEN/TS 14972 (DIN SPEC 91216):2011-09 - Watermist systems

Com­po­nents for water ex­tin­gui­shing systems
'MXD-V13-K1,0-XP'
High pressure water mist nozzle

Related Systems

The water mist nozzle 'MXD-V13-K1,0-XP' may only be used to protect areas of application according to VdS 3188 annex K.2.3:

  • paint booths

    Parameter water mist nozzle:
  • maximum permissible ceiling height: 4,5 m

    Limitations and restrictions:
  • flammable liquids with a flash point greater or equal + 21°C
  • less dangerous liquids with regard to their flammability or their fire behavior
  • The area above the nozzle level must be free of fire loads such as cable ducts (exception: interior protective coverings such as films).

    The annex 3 of the approval and the system-specific manual for planning and installation of the manufacturer must be observed.

Updated at: 18.08.2026
    . up